Permit: T09CM02772

Parcel: 115040150


Addresses:

1345 N 5TH AV #01


Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T09CM02772

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
11/09/2009 ELECTRIC - UFER Approved IVRS - Inspection :*
11/03/2009 ELECTRIC - UFER Partial Approval IVRS - Inspection :*
1) 2 GROUND RODS AT ALL STRUCTURES, GAS AND WATER BOND PER 250 NEC
2) 24" MINIMUM DEPTH FOR DIRECT BURIAL FROM TOP OF CONDUCTORS TO F.G. 300.5 NEC
3) SERVICE EQUIPMENT (ALL IN ONE) CANNOT BE USED AS SUB PANELS FOR #2 AND 3, SEE LISTING INSTRUCTIONS
4) FEEDERS TO HAVE EQUIPMENT GROUND PER 250.32 B1 NEC
5) PLANS/PERMIT TO BE POSTED ON SITE
6) NO INTERIOR INSPECTIONS AT THIS TIME