Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T09CM02765
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/11/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
12/11/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE TRAPS ON INDIRECT DRAINS OVER 5' AND PROVIDE AGS 2) SWEEP AT DW DRAIN 3) ACCESS ABOVE BACKFLOWS FOR SERVICE 4) NON-CARBONATED BEVERAGES REQUIRE BACKFLOW PROTECTION SEPARATE OF CARBONATED C OF O ISSUES: 1) PROVIDE A FLOOR PLAN OF EXISTING FIXTURE HOSE BIBS AND VACUUM BREAKERS 2) CAULKING AT FIXTURES REPLACED 3) PETITION OF APPEAL REQUIRED FOR WATERLESS URINALS 4) PROPER INDIRECT WASTE PIPING WITH MIN AIR GAPS 5) BACKFLOW CERTS FOR EXISTING ASSEMBLIES 6) RECONNECT EQUIPMENT 7) LIST MAY NOT BE COMPLETE |