Permit: T09CM02759

Parcel: 141094500


Addresses:

6370 E BOLDIN DR


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09CM02759

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/16/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) GROUNDING ON PANELS ALL OK
03/12/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PV SYSTEM INSPECTION ONLY
2) GROUND RACK SYSTEM ON ROOF PER INSTRUCTIONS
03/04/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PV SYSTEM INSPECTION ONLY:
1) INSTALLATION TO BE PER PLANS
2) AC & DC DISCONNECTS TO BE GROUPED
3) EACH PANEL AND RAI. TO BE CONNECTED TO EQUIPMENT GROUND
4) LUGS RATED FOR 1 WIRE TERMINATION
5) CONDUCTORS RUN ON ROOF TO BE PROTECTED FROM PHYSICAL DAMAGE
6) INSTALL CHASE NIPPE AT LB CONNECTION TO PANEL
7) INSTALL WIRING LABE AT A/C DISONNECT AND A/C BREAKER THAT TERMINALS MAYBE ENERGIZED ON BOTH ? AND WOOD SIDE
8) INSTALL #8 GEC TO PV INVERTER PER NOT ON SHEET TO BE CONTINOUS