Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM02759
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/16/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) GROUNDING ON PANELS ALL OK |
|
03/12/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PV SYSTEM INSPECTION ONLY 2) GROUND RACK SYSTEM ON ROOF PER INSTRUCTIONS |
|
03/04/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PV SYSTEM INSPECTION ONLY: 1) INSTALLATION TO BE PER PLANS 2) AC & DC DISCONNECTS TO BE GROUPED 3) EACH PANEL AND RAI. TO BE CONNECTED TO EQUIPMENT GROUND 4) LUGS RATED FOR 1 WIRE TERMINATION 5) CONDUCTORS RUN ON ROOF TO BE PROTECTED FROM PHYSICAL DAMAGE 6) INSTALL CHASE NIPPE AT LB CONNECTION TO PANEL 7) INSTALL WIRING LABE AT A/C DISONNECT AND A/C BREAKER THAT TERMINALS MAYBE ENERGIZED ON BOTH ? AND WOOD SIDE 8) INSTALL #8 GEC TO PV INVERTER PER NOT ON SHEET TO BE CONTINOUS |