Permit: T09CM02686

Parcel: 13315299A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
09/23/2010 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
09/14/2010 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) POINT OF VENT SHALL BE TAKEN OFF ABOVE THE FLOW LINE, DOWN STREAM OF TRAP
2) POINT OF VENT SHALL BE ABOVE WEIR OF TRAP
3) PROVIDE DRAINAGE FITTINGS ON ? INDIRECT WASTE PIPING
4) PROVIDE CLEANOUTS
5) INDIRECT WASTE PIPING OVER 5' REQUIRES A P TRAP
6) SEAL ALL THREADS
7) ICE BIN DRAINS MAY NOT COMBINE, ALSO NEED TRAPS AND CLEANOUTS MINIMUM SIZE REQUIRED IS 3/4
8) SUPPORT GAS PIPING AT CONNECTIONS, NOT TO EXCEED 8'
9) SECURE RISER AT SOV
10) REPLACE USED FLEX
11) PROVIDE A 10 PSI TEST