Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T09CM02678
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/08/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) 14 PSI TEST IS OK 2) AIR BALANCE OK |
|
02/05/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) 1/2" I.D. X 36" GAS FLEX NOT ADEQUATE FOR 250,000 BTU PAINT EXPOSED PVC WITH LATEX PAINT 2) PROVIDE AIR BALANCE REPORT |
|
02/01/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. CONDENSATE CANNOT TERMINATE ONTO A HARD SURFACE. 2. PROVIDE THE REQUIRED GAS ISOMETRIC DRAWING FOR ENTIRE GAS LINE & ADD PLUMBING TO EXISTING PERMIT. 3. GAS FLEX CONNECTORS NOT SIZED CORRECTLY TO THE 2 LARGE UNIT ON THE ROOF. 4. PROVIDE AIR BALANCE REPORT. |
|
01/29/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CONTRACTOR NOT ON SITE PROVIDE ACCESS TO ROOF |
|
01/21/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE TIME CLOCKS FOR BATHROOM EXHAUST 2) TERMINATE EXHAUST DUCTS TO OUTDOORS 3) PROVIDE PERMITS FOR ALL A/C UNITS ON ROOF 4) UNITS WERE INSTALLED WITHOUT PERMITS AND INSPECTIONS 5) BRING ALL UNITS UP TO CODE |