Permit: T09CM02678

Parcel: 130140260


Addresses:

4082 E 22ND ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T09CM02678

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/08/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) 14 PSI TEST IS OK
2) AIR BALANCE OK
02/05/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) 1/2" I.D. X 36" GAS FLEX NOT ADEQUATE FOR 250,000 BTU PAINT EXPOSED PVC WITH LATEX PAINT
2) PROVIDE AIR BALANCE REPORT
02/01/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. CONDENSATE CANNOT TERMINATE ONTO A HARD SURFACE.
2. PROVIDE THE REQUIRED GAS ISOMETRIC DRAWING FOR ENTIRE GAS LINE & ADD PLUMBING TO EXISTING PERMIT.
3. GAS FLEX CONNECTORS NOT SIZED CORRECTLY TO THE 2 LARGE UNIT ON THE ROOF.
4. PROVIDE AIR BALANCE REPORT.
01/29/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONTRACTOR NOT ON SITE
PROVIDE ACCESS TO ROOF
01/21/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE TIME CLOCKS FOR BATHROOM EXHAUST
2) TERMINATE EXHAUST DUCTS TO OUTDOORS
3) PROVIDE PERMITS FOR ALL A/C UNITS ON ROOF
4) UNITS WERE INSTALLED WITHOUT PERMITS AND INSPECTIONS
5) BRING ALL UNITS UP TO CODE