Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T09CM02678
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/21/2010 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
01/20/2010 | PLUMBING - INTERMEDIATE | Partial Approval | EXPOSE ALL CLOSET FLANGES PER 1/11/10 INSPECTION REQUEST | |
01/11/2010 | PLUMBING - INTERMEDIATE | Partial Approval | 1) WATER TEST DWV AT BREAKROOM SINK AND H20 PIPING OK 2) NEED TO SEE CLOSET FLANGE INSTALLATION PRIOR TO SETING STOOLS |
|
01/07/2010 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE LONG RADIUS DRAWING FITTINGS FOR HORIZONTAL CHANGE OF DIRECTION AT LAVS & AT BREAK ROOM SINK AND RETEST. |
|
11/24/2009 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE APPROVED DRAINAGE FITTINGS, SUPPORT OVERHADE PIPING AT CORRECT INTERVALS. INSTALL PER APPROVED PLAN OR MINIMUM RED LINE ALL CHANGES, PROVIDE WATER HAMMER ARRESTORS FOR QUICK CLOSING VALVES 2) PROVIDE DRAINAGE FITTING FOR URINAL 3) HAVE A PLUMBER ON SITE FOR NEXT INSPECTION OR YOU WILL BE REFEE'D |