Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM02678
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/28/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/21/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PREVIOUS INSPECTION ITEMS CORRECTED, NEED TO SUBMIT RED LINE DRAWINGS FOR APPROVAL BY CITY |
|
01/20/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REVISED PLANS NEED TO GO THRU PLAN REVIEW AND BE APPROVED 2) EM LIGHTING TO BE POWERED FROM SAME PANEL AS LIGHTING IN AREA. NEED LOCK ON DEVICE 3) NEED UPDATED PANEL SCHEDULES 4) CLOSE OPEN KNOCKOUTS IN PANELS 5) LB MISSING COVER AND STRAP EMT WITHIN 3' AT PANEL 6) INSTALL ALL MOUNTING SCREWS FOR RECEPTS IN INDUSTRIAL COVERS 7) NEED REVISED LIGHTING PLANS AND RISER PLANS |