Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/27/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) OK FOR FINAL |
|
| 07/07/2010 | MECHANICAL - FINAL | Partial Approval | 1) COVER CANVAS, ROOF JACK FOR LAV VOLTAGE AND SLEEPERS 2) PROTECTIVE COATING ON ARMAFLEX, FUSES ? DISCONNECT, MARK DATA PLATE, ECONOMIZER AND FAN COIL 3) 1ST FLOOR TRAP REVERSED, NO PRIMER, NO OVERFLOW SENSOR, MARK DATA PLATE AND NO CEILING IN FAN ENCLOSURE 4) 2ND FLOOR NEEDS TO BE COMPLETED 5) PROVIDE AIR BALANCE REPORT |
|
| 07/06/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/21/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) CHECKED EXHAUST DUCTING IN WALL-OK TO COVER |