Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T09CM02664
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/20/2010 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* 1) REVISE PLANS TO SHOW THE ACTUAL DUCT SYSTEM INSTALLED 2) SHOW HOW RETURN AIR ON 1ST FLOOR WILL BE TERMINATED 3) LEAVE OFF SHEETROCK 2ND FLOOR EXHAUST TERMINATION |
|
04/07/2010 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SEAL ALL JOINTS ON METAL DUCTING. 1ST FLOOR DUCTING REQUIRE MIN R 4.2 INSULATION. ROOFTOP DUCTING REQUIRES MIN R8 ALL DUCT TAPE TO BE UL 181 LISTED TAPE. PROVIDE PANDUIT STRAPS AT ALL FLEX DUCT CONNECTIONS. INSTALL BATHROOM EXHAUST DUCTS. REVISE PLANS IF CHANGING EQUIPMENT. INSTALL REFER LINE SETS. INSULATE PER NOTE 2.10 M-2 |
|
04/06/2010 | MECHANICAL - INTERMEDIATE | Cancelled | CANCELLED PER CONTRACTOR JASON #445-0762 | |
04/06/2010 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
04/05/2010 | MECHANICAL - INTERMEDIATE | Cancelled | CANCELLED PER CONTRACTOR JASON #445-0762 | |
04/05/2010 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) CONTRACTOR CANCELLED |