Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM02664
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/11/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/27/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY CONTRACTOR |
|
07/08/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE REVISED PLANS ON FULL SHEET. NEED LOAD CALCS FOR EACH PANEL 2) INSTALL BONDING SCREW FOR A/C DISCONNECT 3) GFI PROTECT KITCHEN COUNTER RECEPTS AND INSTALL MICROWAVE RECEPT 4) INSTALL PROPER BREAKERS AND NEED GFI PROTECTION FOR GARAGE 5) PROPER FUSING AND MARKING FOR A/C EQUIPMENT 6) I HAVE NO ISSUES WITH TCO FOR FIRST FLOOR, NEED TO CHECK WITH BLDG INSPECTOR |
|
07/02/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NEED REVISED PLANS FOR ALL CHANGES 2) NO FINAL INSPECTIONS WILL BE DONE UNTIL APPROVED 3) REVISED PLANS ARE ON SITE |