Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM02664

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/08/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/07/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/07/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS & CEILINGS NEED LIGHT FIXTURES & DOORWAYS AS DISCUSSED. NEED REVISED PLANS.
04/06/2010 ELECTRIC - INTERMEDIATE Cancelled CANCELLED PER CONTRACTOR JASON #445-0762
04/05/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ARMOR ON MC CABLE AT CLOSET/GARAGE WALL BROKEN
2) SEAL OPEN KNOCKOUTS IN BOXES
3) INSTALL MUD RINGS ON BOXES
4) LIGHT BOXES NOT SECURED IN RESTROOMS
5) NEED REVISED PLANS ?, BEEN 8 WEEKS
6) MC CABLES HANGING/NOT TERMINATED ?
7) PROTECT CABLES WITHIN 1 1/4" FROM EDGE OF STUD
8) WIRING TO RESIDENCE NOT COMPLETED
9) NEED PROPER RECEPT SPACING IN RESIDENCE
10) NEED OUTDOOR LIGHT AT ENTRANCE TO RESIDENCE AND GARAGE
11) HAVE ELECTRICAL CONTRACTOR GO THRU AND INSTALL PER PLAN & NEC