Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/08/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/07/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 04/07/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS & CEILINGS NEED LIGHT FIXTURES & DOORWAYS AS DISCUSSED. NEED REVISED PLANS. |
|
| 04/06/2010 | ELECTRIC - INTERMEDIATE | Cancelled | CANCELLED PER CONTRACTOR JASON #445-0762 | |
| 04/05/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ARMOR ON MC CABLE AT CLOSET/GARAGE WALL BROKEN 2) SEAL OPEN KNOCKOUTS IN BOXES 3) INSTALL MUD RINGS ON BOXES 4) LIGHT BOXES NOT SECURED IN RESTROOMS 5) NEED REVISED PLANS ?, BEEN 8 WEEKS 6) MC CABLES HANGING/NOT TERMINATED ? 7) PROTECT CABLES WITHIN 1 1/4" FROM EDGE OF STUD 8) WIRING TO RESIDENCE NOT COMPLETED 9) NEED PROPER RECEPT SPACING IN RESIDENCE 10) NEED OUTDOOR LIGHT AT ENTRANCE TO RESIDENCE AND GARAGE 11) HAVE ELECTRICAL CONTRACTOR GO THRU AND INSTALL PER PLAN & NEC |