Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/07/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) RECEPT OVER TO BE WEATHER PROOF WHETHER OR NOT PLUGGED INTO 406.8 2) CANNOT USE SHEET METAL THREADED SCREWS FOR GROUNDING 250.8 3) TIGHTEN LOOSE FITTINGS 4) PLANS CALL FOR BONDING FITTING BOX CONNECTIONS |
|
| 11/30/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) REVISE ELECTRIC ONE LINE TO REFLECT EQUIPMENT INSTALLED 2) LABEL EQUIPMENT |
|
| 10/23/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK 1 1/1" STUB UP AT PARKING STRUCTURE, 4 TOTAL. 2. OK UFFR CONNECTION TO J BOLTS FOR CANOPY |