Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T09CM02647
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/10/2009 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
10/29/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK CONTINUATION OF U.G. RACEWAYS TO BLDG 2) GROUND ROD LAYING IN TRENCH DOES NOT MEET NEC REQUIREMENTS. NEC REQUIRES PER GROUNDING ELECTRODES AT BLDG TO BE CONNECTED TOGETHER TO FORM GROUNDING ELECTRODE SYSTEM |
|
10/23/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
10/14/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 4-1'=DC 3/4-1 FOR CHARGERS OTHER 3/4 FOR GROUND WIRES 2) UFER ALL PVC 3) ? ? 1' + 1-3/4 ALL PVC 20' NORTH OF CANOPY |