Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/08/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FLEX DUCT TO BE INSTALLED PER DETAIL A/M2.O 2) ALL FLEX CONNECTIONS TO BE A MINIMUM OF 2" BEADED CONNECTION 3) FLEX CONNECTORS NOT PROPERLY INSTALLED 4) PROVIDE ACCESS TO VAV CONTROL BOX'S |