Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T09CM02626
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/09/2010 | PLUMBING - INTERMEDIATE | Approved | ||
05/21/2010 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 2 SHOWER PANS OK |
|
05/10/2010 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ABS THRU ROOF OK 2) COPPER AND INSULATION OK |
|
04/23/2010 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DWV THRU ROOF OK 2) WATER OK-RESECURE INSULATION TO PIPING 3) PROVIDE SHOWER DETAIL-SHOW LINER, SECURING METHOD, AND ALL REQUIREMENTS |
|
04/16/2010 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DWV THRU ROOF WATER TEST OK 2) WATER DISTRIBUTION TO EAST EDGE OF ROOF TEST OK 3) NEED 8" IN AND OUT OF WATER HEATER INSULATED PRIOR TO COVERING, PIPING EXPOSED TO FREEZING REQUIRES INSULATION WITH INSPECTION 4) NEED TO SEE SHOWER PAN LINER WITH TEST PRIOR TO ANY FLOORING NOTE: WATER HEATER REQUIRES CLEARANCES FROM OPENABLE WINDOWS AND OVERHANGS ON ROOF |
|
03/26/2010 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DEMO 2ND LEVEL OK 2) WATER TEST 2ND FLOOR RESTROOM WITH SINGLE 3" STACK USED FOR (2) HORIZONTAL STOOL CARRIERS OK PENDING RED LINE ON SITE |