Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/03/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 02/18/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE 24 GA S.M. STRAPS AND SADDLES PER PLANS AND SPECS 2) FLEX DUCT NOT TO EXCEED 5' PER SPECS 3) INSULATE BRANCH TAPS 4) FLEX TO BE INSTALLED PER PLANS/DETAILS 5) PROVIDE MINIMUM 2" BEADED COLLARS AT FLEX CONNECTIONS PER MANUFACTURE INSTALLATION INSTRUCTIONS |