Permit: T09CM02620

Parcel: 132166450


Addresses:

4600 S PARK AV #08

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
03/03/2010 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
02/18/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE 24 GA S.M. STRAPS AND SADDLES PER PLANS AND SPECS
2) FLEX DUCT NOT TO EXCEED 5' PER SPECS
3) INSULATE BRANCH TAPS
4) FLEX TO BE INSTALLED PER PLANS/DETAILS
5) PROVIDE MINIMUM 2" BEADED COLLARS AT FLEX CONNECTIONS PER MANUFACTURE INSTALLATION INSTRUCTIONS