Permit: T09CM02608

Parcel: 13632005B

Inspection Status: Cancelled

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/10/2011 ELECTRIC - FINAL Cancelled IVRS - RI canceled
09/29/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) GAS LINE PRESSURE TEST 10 POUNDS FOR 15 MIN.
2) OPEN TAPE JOINT WEST FURNACE SINGLE TO DBL
3) ALL SUB-PANELS REQUIRE NEUTRALS AND GROUNDS ISOLATED
4) SUB PANEL WEST SIDE NO GROUND, 15A GRD ROD OK ?
5) BOND ALL GROUND BUSSES TO METAL CABINET
6) ALL UNDERGROUNDED CIRCUITS TO BE GFCI PROTECTED OR TWO PRONG RECEPTS REQUIRED
7) STICK UP SMOKE DETECTORS IN ALL BEDROOMS AND ONE IN HALLWAY
8) NEED GFCI PROTECTION FOR ALL KIT COUNTER RECEPTS AND BATHROOM RECEPTS