Inspection History Details
Inspection Status: Cancelled
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/10/2011 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
| 09/29/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) GAS LINE PRESSURE TEST 10 POUNDS FOR 15 MIN. 2) OPEN TAPE JOINT WEST FURNACE SINGLE TO DBL 3) ALL SUB-PANELS REQUIRE NEUTRALS AND GROUNDS ISOLATED 4) SUB PANEL WEST SIDE NO GROUND, 15A GRD ROD OK ? 5) BOND ALL GROUND BUSSES TO METAL CABINET 6) ALL UNDERGROUNDED CIRCUITS TO BE GFCI PROTECTED OR TWO PRONG RECEPTS REQUIRED 7) STICK UP SMOKE DETECTORS IN ALL BEDROOMS AND ONE IN HALLWAY 8) NEED GFCI PROTECTION FOR ALL KIT COUNTER RECEPTS AND BATHROOM RECEPTS |