Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/10/2011 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 10/07/2009 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* 1) NEED SMOKIES IN BEDROOM AND HALL 2) GFCI IN KIT BATHROOM 3) DISCONNECT POOL CIRCUIT AT GARAGE SUB PANEL 4) DBL CYLINDER DEAD BOLTS ARE NOT APPROVED FOR EGRESS DOORS 5) GROUND MAIN SUB PANEL WITH H20 GAS BOND |
|
| 10/06/2009 | ELECTRIC - RECONNECT | Denied | 1) MAIN SERVICE PANEL HOUSE NOT GROUNDED, REQUIRES 2 GROUND RODS, GAS AND WATER BOND 2) MAIN SERVICE PANEL TO BE RIGIDLY SUPPORTED 3) THERE IS NO EQUIPMENT GROUND RUNNING TO ANY SUB PANELS 4) NEUTRALS AND GROUNDS TO BE INSTALLED 5) RESIDENCE HAS GROUNDED OUTLETS WITH NO VIABLE GROUND 6) SUB PANEL IN GARAGE-REMOVE IMPROPERLY TERMINATED CONDUCTORS-NEUTRALS AND GROUNDS, REMOVE CIRCUIT USING GREEN WIRE AS NEUTRAL 7) SEAL UNUSED HOLES 8) SUB PANEL ISOLATE GROUND AND NEUTRALS (WEST END OF HOUSE) 9) GFI MAIN BREAKERS AT MAIN PANEL MAY BE USED 10) GROUND WIRES AT SUB PANELS TO WATER LINES |