Permit: T09CM02601

Parcel: 140220570

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T09CM02601

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/04/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/03/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ACCESS CODE WRONG
10/23/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO ACCESS
10/20/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE GROMETTS AT L.V. ENTERING INDOOR UNTI AND REF. PIPING ENTERING COIL
2) ITEMS DATED 10/06/09 #2,3,7,9 & 10 CORRECTED, ALL OTHERS NEED TO BE ADDRESSED
10/06/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FLUE PIPING NOT PROPERLY INSTALLED
2) PROVIDE SECONDARY DRAIN TO APPROVED LOCATION
3) ALL PVC JOINTS TO HAVE PRIMER
4) COIL TO BE PROPERLY ATTACVHED TO DUCT. PROVIDE MECHANICAL FASTENERS, NO TAPE
5) RETURN DUCT NOT MECHANICALLY ATTACHED
6) PROVIDE APPROVED RETURN DUCT SIZE INCREASE X 2"
7) PROVIDE BUG SCREEN AT COMBUSTION AIR INTLETS
8) T-STAT WIRING EXPOSED TO EXTERIOR MUST BE PROTECTED
9) CONDENSING UNIT OVER FUSED
10) CONDENSATE PIPING TO BE RUN AS NOT TO BLOCK UNIT ACCESS DOOR