Permit: T09CM02597

Parcel: 127031330


Addresses:

5846 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
05/06/2010 FIRE - FINAL Approved
12/24/2009 FIRE - FINAL Denied 1. Wiring to cabinets on sales floor shall be protected to NEC code.
2. Yellow extension cord to cigar cabinet not allowed.
3. Back packaging/storage room wiring out of 6' ceiling light shall repair or replace.
4. In office cover missing on 4sq box wiring hanging out.
5. All hoses to torches not allowed for propane shall use only proper hose for propane gas.
6. Need no smoking signs posted where propane bottles are placed.
7. Shall keep propane to 200 water gallons in building need to show inspector how much is in building now.
10/01/2009 FIRE - FINAL Denied 1. Wiring to cabinets on sales floor shall be protected to NEC code.
2. Yellow extension cord to cigar cabinet not allowed.
3. Electrical cord through door way to break room not allowed and power strips are missing ground lugs replace power strips.
4. Electrical wire to sale cabinet on southwest sales floor shall be protected per NEC codes and no wire splices are allowed on back of cabinets.
5. Extension cord to soda machine not allowed all power strips shall be plugged into an outlet and not tandem plugging of power strips allowed.
6. Back packaging/storage room wiring out of 6' ceiling light shall repair or replace.
7. In office cover missing on 4sq box wiring hanging out.
8. All hoses to torches not allowed for propane shall use only proper hose for propane gas.
9. Need no smoking signs posted where propane bottles are placed.
10. Shall keep propane to 200 water gallons in building need to show inspector how much is in building now.