Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/02/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) OK FOR FINAL |
|
| 05/26/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) DUCT SMOKE DETECTOR TEST IS OK 2) A/C 1, 2 & 5 MISSING OUTSIDE AIR INTAKE 3) PROVIDE AND RE-BALANCE OUTSIDE AIR 4) EVERYTHING ELSE IS OK |
|
| 04/30/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CONDENSATE ON RTU VENTED INCORRECTLY 2) WASTE VENT TO CLOSE TO RTU O.S.A. INLET 3) PROVIDE DUCT SMOKE DETECTOR TEST REPORT X3 4) PROVIDE AIR BALANCE REPORT |