Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* PROVIDE CONDENSATE FOR A/C IN PHONE ROOMS & SUPPORT LINE SET. WILL CHECK ON FINAL. |
|
| 03/02/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) CAP OFF VENTS UPSTREAM OF CONDENSATE TRAPS 2) RELOCATE ANY DISCONNECT MIN 36" FROM ANY SERVICE ACCESS PANEL 3) PERMANENTLY ID A/C UNITS 4) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX 5) 1/2" ID GAS FLEX NOT ADEQUATE FOR 250,000 BTU 6) ALL OTHER GAS CONNECTIONS ARE OK |
|
| 12/30/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SUPPLY & EXHAUST IN RESTROOMS OK TO SHEET ROCK, PROVIDE BACKING AROUND CEILING BOXES |