Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HYDRONIC PIPING
Permit Number - T09CM02583
Inspection Description - MECHANICAL - HYDRONIC PIPING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/22/2010 | MECHANICAL - HYDRONIC PIPING | Approved | IVRS - Inspection :* | |
09/21/2010 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* | |
09/20/2010 | MECHANICAL - HYDRONIC PIPING | Not ready for Inspection | IVRS - Inspection :* | |
09/17/2010 | MECHANICAL - HYDRONIC PIPING | Not ready for Inspection | IVRS - Inspection :* 1) CONDENSATE NOT INSULATED PER PLANS 2) PROVIDE 12" SADDLES PER PLANS 3) LINE SETS NOT PROPERLY INSULATED 4) SEAL ALL DUCT JOINTS 5) ALL T-BAR REGISTERS TO BE TIED TO STRUCTURE 6) O.S.A. DUCT SUPPORTED BY REF. LINE SETS NOT ALLOWED 7) RETURN PLENIUMS NOT SUPPORTED PROPERLY 8) PROVIDE HANGERS, SECONDARY DRAIN PAN IS NOT AN APPROVED MEANS OF SUPPORT 9) FLEX DUCT OVER 5' TO HAVE SUPPORT PER PLANS 10) NOTHING ON SPRINKLER |