Permit: T09CM02583

Parcel: 125076370

Inspection Status: Approved

Inspection History: MECHANICAL - HYDRONIC PIPING

Permit Number - T09CM02583

Inspection Description - MECHANICAL - HYDRONIC PIPING

Inspection Status - Approved

Date Description Inspector Results Comments
09/22/2010 MECHANICAL - HYDRONIC PIPING Approved IVRS - Inspection :*
09/21/2010 MECHANICAL - HYDRONIC PIPING Partial Approval IVRS - Inspection :*
09/20/2010 MECHANICAL - HYDRONIC PIPING Not ready for Inspection IVRS - Inspection :*
09/17/2010 MECHANICAL - HYDRONIC PIPING Not ready for Inspection IVRS - Inspection :*
1) CONDENSATE NOT INSULATED PER PLANS
2) PROVIDE 12" SADDLES PER PLANS
3) LINE SETS NOT PROPERLY INSULATED
4) SEAL ALL DUCT JOINTS
5) ALL T-BAR REGISTERS TO BE TIED TO STRUCTURE
6) O.S.A. DUCT SUPPORTED BY REF. LINE SETS NOT ALLOWED
7) RETURN PLENIUMS NOT SUPPORTED PROPERLY
8) PROVIDE HANGERS, SECONDARY DRAIN PAN IS NOT AN APPROVED MEANS OF SUPPORT
9) FLEX DUCT OVER 5' TO HAVE SUPPORT PER PLANS
10) NOTHING ON SPRINKLER