Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/19/2009 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* 1) OK FOR TILES |
|
| 10/14/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) RECEIVED ENGINEERS APPROVAL ON FOLLOWING: OK TO FLEX LENGTH UP TO 10' PROVIDED SYSTEM WILL BALANCE, OK WRAP DUCT IN LIEU OF ACOUSTIC LINING AND ITEMS 2 THRU 5 DATED 10/08/09 OK |
|
| 10/08/2009 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DUCT WORK IS OUTSIDE THERMAL ENVELOPE, PROVIDE MIN. R-8 BETWEEN DUCT INTERIOR AND EXTERIOR OF BLDG 2) CEILING BOXES TO HAVE ACOUSTIC LINER PER DETAIL (1) MP1.0 3) RECTANGULAR DUCT TO BE LINED PER DETAIL (5) MP1.0 AND SPEC SECTION 5-A.1 4) FLEX DUCT NOT TO EXCEED 5' PER SPEC SECTION 14-A 5) PROVIDE A MEANS TO BALANCE AIR DIST. SYSTEM PER SPEC. SECTION 4-?.2 |