Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/29/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 1 1/2" EMT CONDUIT ABOVE PANEL BY METER NOT SUPPORTED PROPERLY-SHOULD HAVE OFF SET ON CONDUIT, 1-HOLE STRAP PULLING OUT (PLASTIC ANCHOR) ALSO ON ROOF 2) 1" CONDUIT ON ROOF BELOW J-BOX HAS KINK ON 90 DEGREE BEND NOT PROPERLY SECURED TO WALL 3) NEED #8 CU GEC TO MAIN SERVICE |