Permit: T09CM02509

Parcel: 12111190A


Addresses:

4826 E PIMA ST

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
02/04/2010 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
02/01/2010 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE INTERCEPTOR MODEL NUMBER AS A REDLINE ON THE PLANS
2. PROVIDE A TEST ON PIPING INCLUDING INDIRECT DRAIN IN WALL
01/27/2010 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) IF GT HAS AN INTEGRAL FLOW CONTROL PROVIDE MODEL NUMBER AND INSTALL PER ROCKFORD INSTRUCTIONS
2) RED LINE ALL CHANGES ON APPROVED PLAN
3) A VENT CONNECTION MUST RISE AT A MINIMUM OF 45 DEGREE SO THAT THE VENT TAKE OFF IS ABOVE THE FLOW LINE
4) SWEEP REQUIRED AT VERTICAL TO HORIZONTAL CHANGE OF DIRECTION
5) INSTALL FOAM WRAPS AND PIPE INSULATION