Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/12/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO POWER TO BIG OFFICE 2) INSTANT HOTS NOT ON PLANS. INSTALL DISCONNECTING MEANS NEC 422 3) HALL EM LIGHTS TO BE ON HALL CIRCUIT 4) INSTALL TIME LOCK FOR BATH EXHAUST FANS SEE SHEET M-1 5) INSTALL SPLIT BREAKERS IN PROPER POSITIONS IN PANEL SEE SCHEMATIC 6) INSTALL EQUIPMENT GROUND AT GAS PACK WEST UNIT 7) SECURE RACEWAYS PENETRATING ROOF |