Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T09CM02469
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/12/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
01/11/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUNDING ELECTRODE CONDUCTOR AT BONDING JUMPERS FOR PIPING SYSTEMS CUT AND STOLEN. NEEDS TO BE REPLACED 2) HAVE ELECTRICAL CONTRACTOR ON SITE TO OPEN ALL SERVICE EQUIPMENT 3) NEED TO INSTALL BONDING JUMPERS IN METERS AND REMOVE EQUIPMENT GROUNDS IN SERVICE EUIPMENT GIVING PARALLEL NEUTRAL PATHS |