Permit: T09CM02469

Parcel: 130140260


Addresses:

4056 E 22ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T09CM02469

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
01/12/2010 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
01/11/2010 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUNDING ELECTRODE CONDUCTOR AT BONDING JUMPERS FOR PIPING SYSTEMS CUT AND STOLEN. NEEDS TO BE REPLACED
2) HAVE ELECTRICAL CONTRACTOR ON SITE TO OPEN ALL SERVICE EQUIPMENT
3) NEED TO INSTALL BONDING JUMPERS IN METERS AND REMOVE EQUIPMENT GROUNDS IN SERVICE EUIPMENT GIVING PARALLEL NEUTRAL PATHS