Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* NSTALL MISSING PIPE CLAMPS AND REPLACE UNDER SIZED CONDUIT CLAMPS ON WATER PIPING W/PIPE CLAMPS THAT WON'T DAMAGE INSULATION |
|
| 09/30/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE CALL IN ALL INSPECTIONS 01090, 02090, 03090 FOR FINAL INSPECTION 2) ALL PIPING ON ROOF TO BE SUPPORTED AT CORRECT INTERVALS AND SECURED TO SUPPORTS 3) ALL PIPE AND CONDUIT PENETRATIONS THRU ROOF REQUIRE ROOF FLASHINGS 4) FASTENERS FOR SUPPORTS FOR TANK/PANEL TO BE PER APPROVED PLAN (181-5 WIND LOAD CALCULATIONS) (TYPICALLY ROOF SLEEPERS ARE NOT PARALLEL TO ROOF JOISTS) 5) PROVIDE CORRECT WEATHER PROOF CONNECTORS TO PANEL AND HEATER PER CONDUIT 6) PROVIDE A MEANS OF DISCONNECT FOR NEW WATER HEATER THAT IS ELECTRICAL 7) PLAN REQUIRES 310 WIRE AND CORRECT COLOR OF WIRE WITH 30 AMP BREAKER COMPATIBLE WITH SERVICE PANEL 8) PROVIDE PULL BOXES AT CORRECT INTERVALS FOR WIRING 9) PROVIDE PERMANENT CAP ON GAS PIPING SYSTEM AT OLD GAS WATER HEATER LOCATION 10) PROVIDE DIELECTRIC PROTECTION AT GALVANIZED TO COPPER WATER CONNECTIONS AT OLD WATER HEATER LOCATION 11) SOFT COPPER AT OLD WATER HEATER LOCATION TO + FROM ROOF TOP IS DAMAGED (KNICKED) 12) LIST NOT COMPLETE |