Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) PLUMBERS TAPE IS NOT APPROVED, PROVIDE PLUMBING CLAMPS APPROVED FOR USE AND SIZED CORRECTLY |
|
| 11/13/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) 2 PM NOT READY-CORRECTING LEAK AND MORE |
|
| 10/30/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/29/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TYPE M COPPER IS NOT ALLOWED OUTSIDE OF BLDG 2) ALL PIPING SHALL BE PROPERLY SUPPORTED AND SECURED WITH CLEARANCE ABOVE ROOF TO ALLOW FOR MAINTENCE 3) FLASHINGS ARE NOT PROPERLY SEALED 4) INSULATION WILL REQUIRE INSTALLATION PER MANUFACTURE SPECS AFTER PIPING REINSPECTION 5) T & P LINE NOT SOLDERED OR PROPERLY TERMINATED 6) HAVE A PLUMBER SEE THE UPC FOR INSTALLATION REQUIREMENTS OF PLUMBING SYSTEM 7) REMOVE ABANDONED GAS WATER HEATER VENT TEE, GAS COCK AND PIPING 8) CAP AT MAIN 9) SOAP TEST 10) CAP ABANDON T & P DELECTRIC PROTECTION IS REQUIRED WHEN CONNECTIONS TO GALVANIZED |