Permit: T09CM02458

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T09CM02458

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/16/2009 ELECTRIC - ABOVE CEILING Approved
11/05/2009 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) NEED TO SEE TERM IN J-BOX FOR CASH WRAP AND SIGN SWITCH-ALL ELSE OK
11/04/2009 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) SUPPORT J-BOXES PER 300.11 NEC MC CABLES PER 330 NEC WITHIN 12" AND 6'
2) SUPPORT WIRES TO BE TIED OFF AT BOTH ENDS
3) COMPLETE MC TERMINATIONS