Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T09CM02458
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/16/2009 | ELECTRIC - ABOVE CEILING | Approved | ||
11/05/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) NEED TO SEE TERM IN J-BOX FOR CASH WRAP AND SIGN SWITCH-ALL ELSE OK |
|
11/04/2009 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) SUPPORT J-BOXES PER 300.11 NEC MC CABLES PER 330 NEC WITHIN 12" AND 6' 2) SUPPORT WIRES TO BE TIED OFF AT BOTH ENDS 3) COMPLETE MC TERMINATIONS |