Permit: T09CM02433

Parcel: 134113510


Addresses:

8318 E 18TH ST

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
07/13/2010 BUILDING - FINAL Approved IVRS - Inspection :*
07/12/2010 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) NO ONE PRESENT FOR ACCESS 9:15 AM-RECALL
05/18/2010 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/14/2010 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WIRING FROM SERVICE PANEL TO NEW SUB PANEL 4 WIRES LEAVING SERVICE UP TO ROOF AT 1ST L.B. THERE ARE ONLY 3, 2 POLE BREAKER, DO NOT NEED 220 TO SUB PANEL, ONLY 110, WHAT HAPPENED TO 4TH WIRE ? WIRE IN SERVICE PANEL UP THRU CONDUIT IS #8 CU AT 1ST L.B. HAS ALREADY CHANGED TO #10 ?
2) LABEL ALL CIRCUITS IN SUB PANEL
3) DO NOT DBL TAP BREAKERS, ON WIRE ON ONE BREAKER
4) SUPPORT ROOF CONDUIT EVERY 6'-0" (BLK. 1 1/2" GLUE TO ROOF)
5) GLUE ALL JOINTS
6) BEDROOM SUB PANEL NOT WIRED CORRECTLY, BREAKERS NOT COMPATIBLE WITH WIRE SIZE, MAIN FEEDER PROBLEMS