Permit: T09CM02423

Parcel: 116193770

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T09CM02423

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/26/2010 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
05/25/2010 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CALLED AT 9:40 AM LEFT MESSAGE, AT 9:50 CALL WAS RETURNED, I WAS TOLD NO ONE COULD BE HERE TILL 10:15 OR SO, COULD NOT WAIT
04/12/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ITEMS 3, 4 & 6 DATED 3/24/10 HAVE BEEN CORRECTED
03/24/2010 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE COPPER CONDENSATE PIPING
2) PROVIDE 1" INSULATION ON CONDENSATE PIPING
3) PROVIDE SEALANT AND METAL BANDS AT ALL FLEX CONNECTIONS PER PLANS
4) PROVIDE OBD'S ON REGISTERS PER PLANS
5) PROVIDE 1" CONDENSATE WHEN TIEING OR MORE UNITS TOGETHER
6) PROVIDE MIN. 3 SCREWS AT ALL DUCT ROUND JOINTS
7) INSTALL CONDENSATE PIPING PER SPECIFIC NOT 11 ADDENDUM 3