Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T09CM02423
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/26/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
05/25/2010 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CALLED AT 9:40 AM LEFT MESSAGE, AT 9:50 CALL WAS RETURNED, I WAS TOLD NO ONE COULD BE HERE TILL 10:15 OR SO, COULD NOT WAIT |
|
04/12/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) ITEMS 3, 4 & 6 DATED 3/24/10 HAVE BEEN CORRECTED |
|
03/24/2010 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE COPPER CONDENSATE PIPING 2) PROVIDE 1" INSULATION ON CONDENSATE PIPING 3) PROVIDE SEALANT AND METAL BANDS AT ALL FLEX CONNECTIONS PER PLANS 4) PROVIDE OBD'S ON REGISTERS PER PLANS 5) PROVIDE 1" CONDENSATE WHEN TIEING OR MORE UNITS TOGETHER 6) PROVIDE MIN. 3 SCREWS AT ALL DUCT ROUND JOINTS 7) INSTALL CONDENSATE PIPING PER SPECIFIC NOT 11 ADDENDUM 3 |