Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T09CM02398
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/04/2010 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
12/29/2009 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* 1) TEST OK 2) AT RELOCATED WATER HEATER, YOU MAY NOT CONNECT TO 1/2" PIPING AT WASHER, PROVIDE FULL SIZE PIPING FROM OLD WATER HEATER LOCATION OR OTHER 2) NEW WATER HEATER REQUIRES TYPE B VENT ABOVE ENCLOSURE 3) PROPER T & P TERMINATIONS AND SEDIMENT TRAP NOTE: 1) WASHER DRAIN IS UNSANITARY, IT HAS NO P TRAP AND A BROKEN CONNECTION TO VENT |
|
12/22/2009 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1) SHOW RELOCATED NEW WATER ON A CITY APPROVED PLAN 2) PROVIDE CORRECTLY SIZED AND INSTALLED PIPING WITH PROPER DIELECTRIC PROTECTION 3) COMPLETE WATER HEATER INSTALLATION 4) CAP PIPING AT ABANDONED GAS FIREPLACE |