Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2012 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 10/01/2012 | BUILDING - FINAL | Not ready for Inspection | CANCELLED | |
| 09/28/2012 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MAINTAIN WORKING AT METER PACKS-RIGHT SIDE TRIP HAZARDS 2) LABEL DISCONNECT BY SERVICE 3) PROPERLY TERMINATE GROUND CONDUCTOR AT WATER HEATER AND TIGHTEN LOOSE FITTINGS 4) RECEPTACLE IN METAL INDUSTRIAL COVER MISSING SCREWS 5) BOXES MORE THAN 1/4" FROM BOX TO SURFACE IN NON COMBUSTABLES INPECTION STOPPED BY SUPERINTENDANT. |