Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T09CM02373

Parcel: 13303301A

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T09CM02373

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
04/26/2012 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
11/23/2011 PLUMBING - YARD WTR LINE/TEST Partial Approval NEED TO SEE CONNECTIONS
11/21/2011 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
1) SIZE DISCREPANCY-BLDG PLAN INIDICATES 2" SERVICE
2) TRACER WIRE REQUIRED
3) SPEC BOOKS SPECIFIES 100 PSI FOR TESTING 3.07
4) PROVIDE A GAUGE FOR TEST PRESSURE VERIFICATION