Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T09CM02371

Parcel: 129022640


Addresses:

2809 E EXETER ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/19/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
01/12/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) W/H FLUE TO CLOSE TO COMBUSTIBLES
2) PROVIDE SEDIMENT TRAP ON WATER HEATER
3) CONDENSATE TO TERMINATE WITHIN 6" OF GRADE, CANNOT TERMINATE AT WASTE VENT
4) ALL PVC EXPOSED TO EXTERIOR IS TO BE PAINTED
5) ALL PVC JOINTS TO HAVE PRIMER PURPLE IN COLOR
6) PROVIDE SERVICE RECEPT WITHIN 25' OF UNIT ON ROOF
7) PROVIDE TRUSS LOAD CALC FORM
8) PROVIDE PROPER COLOR CODE FOR LINE VOLTAGE WIRING
9) PANEL NOT LABELED