Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 01/12/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) W/H FLUE TO CLOSE TO COMBUSTIBLES 2) PROVIDE SEDIMENT TRAP ON WATER HEATER 3) CONDENSATE TO TERMINATE WITHIN 6" OF GRADE, CANNOT TERMINATE AT WASTE VENT 4) ALL PVC EXPOSED TO EXTERIOR IS TO BE PAINTED 5) ALL PVC JOINTS TO HAVE PRIMER PURPLE IN COLOR 6) PROVIDE SERVICE RECEPT WITHIN 25' OF UNIT ON ROOF 7) PROVIDE TRUSS LOAD CALC FORM 8) PROVIDE PROPER COLOR CODE FOR LINE VOLTAGE WIRING 9) PANEL NOT LABELED |