Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T09CM02366
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/03/2009 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
11/16/2009 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE TAPE FROM DUCT JOINTS USE SEALER PER PLANS, SEE SPEC 2.03-M-2 INCLUDING R.T.U.'S 2) ALL EXTERIOR DUCT TO HAVE 2" (R-8) DUCT LINER PER I.E.C.C. 3) ALL EXTERIOR DUCT TO BE COATED PER PLANS 4) VERIFY CURB IS INSULATED PER PLANS 5) ALL PVC PIPE TO HAVE PRIMERED JOINTS, PRIMER TOB E PURPLE IN COLOR PER U.P.C. 6) ALL EXPOSED PVC PIPE TO BE PAINTED PER I.M.C. 7) PROVIDE OUTSIDE AIR INLETS PER I.E.C.C. 8) ELECTRICAL CONDUIT TO BE BLOCKED UP OFF ROOF MINIMUM 1.5" 9) CONDENSATE TO TERMINATE AT AN APPROVED LOCATION, CONDENSATE CANNOT TERMINATE ON A HARD SURFACE, SIDEWALK DRIVEWAY, STREET, ETC... 10) DUCT NOT HUNG PER PLANS PROVIDE ENGINEERS APPROVAL FOR ALL CHANGES TO PLANS |