Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/05/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) OK FOR FINAL |
|
| 02/03/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) CAPTURE AND CONTAINMENT OK 2) PROVIDE AIR BALANCE REPORT 3) HEAT SENSOR OK 4) MARK UNIT DATA PLATE ON A/C UNIT AND FUSE ACCORDINGLY 5) CIRCUIT BREAKER FOR CONDENSOR TO LARGE-15 AMP IS MAX |
|
| 02/02/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER CONTRACTOR |