Permit: T09CM02354

Parcel: 11451142B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM02354

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/05/2010 ELECTRIC - INTERMEDIATE Approved
12/16/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS
NOTE:
1) ALL 15 AND 20 AMP 120V RECEPTS TO BE GFI PROTECTED INSTALLED IN KITCHEN 210.8 (B) NEC
NOTE:
1) BE AWARE RECEPTS UNDER TYPE I HOOD TO SHUT OFF WHEN FIRE SUPPRESSION SYSTEM ACTIVATES