Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/02/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/30/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLAN CALLS FOR REGISTERS TO BE LOCATED 30' ABOVE FINISHED FLOOR, CURRENTLY OUTLET REGISTERS ARE 12' ABOVE FINISHED FLOOR WHICH MAY ACCOUNT FOR THE HIGHER S.P. AND LOWER C.F.M. WHICH IS 25 PERCENT BELOW DESIGN
09/28/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ONE ON SITE, UNABLE TO GAIN ACCESS TO BLDG AT 14:35