Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T09CM02351
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/02/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
09/30/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLAN CALLS FOR REGISTERS TO BE LOCATED 30' ABOVE FINISHED FLOOR, CURRENTLY OUTLET REGISTERS ARE 12' ABOVE FINISHED FLOOR WHICH MAY ACCOUNT FOR THE HIGHER S.P. AND LOWER C.F.M. WHICH IS 25 PERCENT BELOW DESIGN |
|
09/28/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ONE ON SITE, UNABLE TO GAIN ACCESS TO BLDG AT 14:35 |