Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2009 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 09/23/2009 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) TEMPERATURE AND PRESSURE DRAIN PIPING TO BE FULL SIZE (NO FLEX) GRAVITY DRAIN TO DAYLIGHT 6"-24" FROM FINISH GRADE 2) PRESSURE RELIEF ON ROOF TO GRAVITY DRAIN 6"-24" FROM FINISH GRADE SEE 608.4 + 608.5 2006 UPC 3) PLEASE SEE SECTION 414.5 FOR TEMPERATURE CONTROL FOR TUBS NOT TO EXCEED 120 DEGREES. THERE IS A SINGLE HOT CONTROL AT THIS RESIDENCE 4) THERE SHOULD BE A TEMPERING VALVE ON THIS INSTALLATION TO AVOID SCALDING. PLEASE SEE SECTION 101.5.2 FOR SAFETY OF SYSTEMS 5) SECURE AND SUPPORT PIPING FOR SUPPLY FROM PANEL INTO STORAGE TANK. NOTE: ALL CODE SECTIONS FROM 2006 UPC |