Date Description Inspector Results Comments
06/15/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/08/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ONE ON SITE
06/03/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SCREWS THRU TYPE 1 DUCT NOT ALLOWED, REMOVE SCREWS AND WELD HOLES SHUT
2) SMOKE CONTAINMENT TEST OK
3) HOOD SENSOR INTERLOCK OK
4) EXHAUST/MVA INTERLOCK OK