Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/09/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1) OK FOR TILES MECHANICAL ONLY |
|
| 11/02/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) CONDENSATE TO BE RUN DTR PER M1.2-2 2) TERMINATE AT APPROVED LOCATION 3) WASTE VENTS ON ROOF ARE NOT APPROVED LOCATIONS |
|
| 10/29/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |