Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T09CM02277
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/21/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
10/13/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) RE-LOCATE HANGERS TO AVOID RUBBING ON TRUSS 2) OK FOR TILES MECHANICAL ONLY |
|
10/07/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
10/06/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
09/25/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SEAL ALL TAPS WITH HARD CAST PER SPEC 3.04 2) PROVIDE BALANCE DAMPERS IN RETURN PER DETAIL 2 M2.1 3) SEAL ALL DUCT JOINTS PER SPEC 3.03 ( INCLUDING CONNNECTIONS TO F.C. ) 4) CONDENSATE PIPING TO BE INSTALLED PER PLANS |