Permit: T09CM02277

Parcel: 14043011A

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
10/14/2009 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
10/09/2009 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) WHIPS NO TO LAY ON GRID
2) SECURELY ATTACH FIXTURES TO GRID 410.16-MFG CLIPS TO BE EFFECTIVE
3) SUPPORT VDV CABLING 725.14
4) TIGHTEN LOOSE FITTINGS A/C DISCONNECT
5) CORDS NOT ALLOWED ABOVE CEILINGS 400.7 & 8