Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T09CM02277
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/14/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
10/09/2009 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) WHIPS NO TO LAY ON GRID 2) SECURELY ATTACH FIXTURES TO GRID 410.16-MFG CLIPS TO BE EFFECTIVE 3) SUPPORT VDV CABLING 725.14 4) TIGHTEN LOOSE FITTINGS A/C DISCONNECT 5) CORDS NOT ALLOWED ABOVE CEILINGS 400.7 & 8 |