Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T09CM02267
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/26/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/18/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DISCONNECT MISSING BOND BUSHING 250.97 250 VOLTS OR MORE, REJECTION PINS AND WIRES ON LUGS NOT EXTEND UP INTO LUG 2) GROUND RODS AND EQUIPMENT GROUND OK 3) SUB PANEL BROKEN CONCENTRICS BOND BUSHING MISSING, NEUTRAL IS NOT TO BE BONDED 4) GUTTERS NEED TO BE BONDED AND STRAP 1 1/4" |
|
08/05/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
06/14/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WIRING, GROUNDING, BONDING FOR POLE LIGHTS OK |