Permit: T09CM02267

Parcel: 133110010

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM02267

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/26/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/18/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DISCONNECT MISSING BOND BUSHING 250.97 250 VOLTS OR MORE, REJECTION PINS AND WIRES ON LUGS NOT EXTEND UP INTO LUG
2) GROUND RODS AND EQUIPMENT GROUND OK
3) SUB PANEL BROKEN CONCENTRICS BOND BUSHING MISSING, NEUTRAL IS NOT TO BE BONDED
4) GUTTERS NEED TO BE BONDED AND STRAP 1 1/4"
08/05/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/14/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
WIRING, GROUNDING, BONDING FOR POLE LIGHTS OK