Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2010 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 10/16/2009 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) OK GROUND RODS 2) OK GAS AND WATER BOND 3) RECALL AFTER SWING OVER COMPLETE |
|
| 10/07/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL LISTED MAST BRACING. CANNOT USE SMASHED EMT WITH MINNIE 2) GROUND RODS TO BE MINIMUM 6' APART 3) MINIMUM SIZE WATER BOND TO BE #4 |