Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/16/2009 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/24/2009 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A TRAP ON CONDENSATE DRAIN LINE 2) PROVIDE A SECONDARY OVERFLOW SENSOR 3) PRIMARY DRAIN IS CONNECTED TO SECONDARY OUTLET ON COIL 4) PLASTIC CONDENSATE PUMP NOT ALLOWED IN A RETURN PLENIUM 5) PROPERLY SECURE THE DRAIN LINE FROM THE PUMP 6) DO NOT USE PLASTIC HOSE OUTDOORS 7) TERMINATE WITH APPROVED METHODS 8) REMOVE ALL FOIL TAPE FROM THE VENT CONNECTOR 9) PROVIDE A ROMEX CONNECTOR FOR POWER CORD TO FURNACE 10) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE 11) PROPERLY SUPPORT THE ELECTRIC DISCONNECT 12) REPAIR ELECTRIC CONDUIT 13) PROVIDE THE REQUIRED GFI SERVICE RECEPTACLE ON ROOF 14) ID CIRCUIT BREAKER |