Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2010 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/25/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SUPPORT EMT WITHIN 3' OF BOXES 2) FILL UNUSED OPENINGS-DEMO CONDUIT BACK TO LAST BOX 3) MANUFACTURES CLIPS TO BE EFFECTIVE 4) PROPERLY SUPPORT EMT THRU TRUSSES 5) SUPPORT M/C CABLE WITHIN 6' OF LUMINIARE |